Number of poles |
3P |
Rated operational voltage [Ue] |
1000V |
Rated insulation voltage [Ui] |
1000V |
Rated withstand voltage [Uimp] |
8kV |
Rated frequency [Hz] |
50/60Hz |
Maximum operating rate in operating cycles per hour(AC3) |
50/60Hz |
Mechanical durability (mil. operations) |
50/60Hz |
Electrical durability (mil. operations) |
50/60Hz |
Rated operational current (AC-1) |
60A |
Power (AC-1) |
- |
- |
- |
- |
Current (AC-1) |
- |
- |
- |
- |
Motor power (AC-3) |
11kW at 200/240V |
18.5kW at 380/440V |
22kW at 500/550V |
22kW at 690V |
22kW at 1000V |
Motor power (AC-4) |
5.5kW at 200/240V |
11kW at 380/440V |
Rated operational current (AC-3) |
40A at 200/240V |
40A at 380/440V |
32A at 500/550V |
23A at 690V |
17A at 690V |
Rated operational current (AC-4) |
25A at 200/240V |
24A at 380/440V |
Rated operational current (DC-3,5) |
- |
- |
- |
Rated operational current (DC-1) |
- |
Type 2 Coordination |
See the Type 2 Coordination Table in the catalog |
Motor power (UL/CSA) |
3hp at 110~220V for 1 phase motors |
7.5hp at 220~240V for 1 phase motors |
15hp at 200~208V for 3 phase motors |
15hp at 220~240V for 3 phase motors |
30hp at 440~480V for 3 phase motors |
30hp at 550~600V for 3 phase motors |
NEMA size |
30hp at 550~600V for 3 phase motors |
Rated Short-time withstand current |
700A at 1s |
300A at 10s |
190A at 30s |
120A at 1min |
80A at 3min |
65A at 10min |
60A at =15min |
Conductor size (AWG) |
8~6 |
Conductor size (mm2) |
10~16 |
The max. number of conductor |
10~16 |
Conductor type |
Solid, Stranded |
Conductor charateristic |
65/75? Cu-wire only |
Main terminal size |
M5 |
Crimp terminal (mm) |
M5 |
Torque (lb-in) |
M5 |
Torque (Nm) |
M5 |
Torque (kgf.cm) |
M5 |